At NSN Unlimited, we maintain a large database of parts PAM12MG6-25-50VDC, PAM12MG3-25-50VDC, 134-225-101, 134 225 101 with NSN 5925-00-846-2234 used in civil and defense applications for the aerospace, marine, and commercial manufactured by Wood Electric Operations Potter And, Eaton Corporation. Utilize our interface to browse items by part number, part type, manufacturer, and more. Obtain insights on top MRO and FBO services, Manufacturer profiles, and part catalogs.
With an unmatched supply-chain network, we are able to provide expedited shipping and same-day or next-day delivery on qualifying parts.
Ready for a quote? Submit an Instant RFQ today for NSN 5925-00-846-2234.
Alternative NSN: 5925-00-846-2234 |
Item Name: Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 008462234 |
NCB Code: USA (00) |
Manufacturers: Wood Electric Operations Potter And , Eaton Corporation |
Part No | NSN | Item Name | Manufacturer | QTY | RFQ |
---|---|---|---|---|---|
PAM12MG6-25-50VDC | 5925-00-846-2234 | circuit breaker | wood electric operations potter and | Avl | RFQ |
PAM12MG6-25-50VDC | 5925-00-846-2234 | circuit breaker | eaton corporation | Avl | RFQ |
PAM12MG3-25-50VDC | 5925-00-846-2234 | circuit breaker | wood electric operations potter and | Avl | RFQ |
PAM12MG3-25-50VDC | 5925-00-846-2234 | circuit breaker | eaton corporation | Avl | RFQ |
134-225-101 | 5925-00-846-2234 | circuit breaker | eaton corporation | Avl | RFQ |
134 225 101 | 5925-00-846-2234 | circuit breaker | wood electric operations potter and | Avl | RFQ |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
ADAT | BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 1 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES DC SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 120.0 SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
THSD | THREAD SERIES DESIGNATOR | UNC |