MRC | Criteria | Characteristic |
---|---|---|
FEAT | SPECIAL FEATURES | IONIZATION DETECTOR C/O SMOKE SENSOR AND SIGNAL CONDITIONER; IONIZATION AGENT AMERICIUM; SPACE MTD; P40 DEG. F TO P149 DEG. F OPERATING TEMP RANGE; ADJUSTABLE DETECTION AND ALARM LEVELS; ALARM LEVEL PRESET AT 40 PCT DIOCTALPHTHALATE AEROSOL CONCENTRATION PORM 10 PCT STABLE; CURRENT RATINGS FOR 1 TO 5 DETECTORS IN PARALLEL W/TERM. RES 13.5 MA PORM 2.0 MA NON-ALARM COND AND 30.0 MA P10.0 M3.0 MA ALARM COND W/24.0 VDC POWER SUPPLY 3/340.0 OHM SERIES IMPEDANCE,PARALLEL RES; SERIES IMPEDANCE POWER SUPPLY AND ALARM NOT INCL; O/A DIM. 4.125 IN. LG. BY 4.00 IN. W BY 3.781 IN. H |
SR-5 | THE MANUFACTURERS DATA | |
SR-5 | MANUFACTURERS CODE | 12763 |
SR-5 | DESIGN CONTROL REFERENCE | 003464-003 |